Environmental Chambers of the HVAC&R Equipment Performance Group

Large "Truck" Chamber

Chamber Dimensions

  • Length: 14.6 m (48 ft.)
  • Width: 7.3 m (24 ft.)
  • Usable Height: 4.2 m (14 ft.)
  • Door: 3.6 m (12 ft.) x 3.6 m (12 ft.)

The large "truck" chamber provides controlled air conditions from -18.0 °C (0.0 °F) to 65.5 °C (150 °F). The conditioning equipment can remove up to 35 kW (120,000 Btu/h) of heat at a dry-bulb temperature of 35 °C (95 °F) and 50% relative humidity. Full range dry-bulb temperature control of ± 1 °C (2 °F) with relative humidity control better than ± 2 % is possible. At ARI heating and cooling conditions, control of dry-bulb and dewpoint temperatures are better than 0.1 °C (0.2 °F).

 

 

Large Truck Chamber Interior

Large Truck Chamber Exterior

 

Heat Pump Chambers

Indoor Chamber Dimensions

Outdoor Chamber Dimensions

  • Length: 10.6 cm (35 ft.)
  • Length: 6.1 m (20 ft.)
  • Width: 4.2 m (14 ft.)
  • Width: 3.9 m (13 ft.)
  • Usable Height: 3.9 m (13 ft.)
  • Usable Height: 3.9 m (13 ft.)
  • Door: 3.6 m (12 ft.) x 2.4 m (8 ft.)
  • Door: 3.6 m (12 ft.) x 1.6 m (5.5 ft.)

The indoor chamber can provide controlled air conditions for all ARI heating and cooling tests for split-systems, window units, and other unitary equipment throughout the range of 10 °C (50 °F) to 60 °C (140 °F) dry-bulb temperature with relative humidity controlled within ±2 %. The outdoor chamber has a temperature range capability from -18 °C (0 °F) to 60 °C (140 °F) with relative humidity controlled within ± 2%. At ARI heating and cooling conditions, control of dry-bulb and dewpoint temperatures are better than 0.1 °C (0.2 °F). Units with cooling capacities up to 35 kW (120 000 Btu/h) may be tested.

 

Heat Exchanger Under Test

Heat Exchanger Temperature Profile

Frosted Heat Pump

Frosted Heat Pump

 

Appliance Chamber

Chamber Dimensions

  • Length: 3.3 m (11 ft.)
  • Width: 3.0 m (10 ft.)
  • Usable Height: 2.4 m (8 ft.)
  • Door: 86 cm (34 in.) x 198 cm (78 in.)

This chamber is used to test small heating and cooling equipment such as radiators, heat exchangers, water coolers, refrigerators, and control devices. Dry-bulb temperature may be controlled from -18 °C (0 °F) to 65 °C (150 °F) with relative humidity controlled within ± 2 % of setpoint. At ARI heating and cooling conditions, control of dry-bulb and dewpoint temperatures are better than 0.1 °C (0.2 °F). Maximum heat removal from this chamber is 11.7 kW (40 000 Btu/h).

 

 

Instrumented Refrigerator

Refrigerator Being Readied for Testing

Refrigerator in Appliance Chamber

 

 