A Curve Based Mixed System Rating Method for Unitary Air Conditioners


pdf icon A Curve-Based Mixed System Rating Method for Unitary Air Conditioners (2.43 MB)

 

W. Vance Payne and Piotr A. Domanski

NISTIR 7225

Keywords:

air conditioner, cooling capacity, cyclic degradation coefficient, mixed system, rating procedure, SEER

Abstract:

The curve-based method was evaluated based on performance predictions and independent laboratory testing for nine mixed systems.  Capacity predictions were within ±5% of the tested values for six of the mixed systems, and four of the SEER predictions were within ±5% of the tested SEERs.  Predictions for SEER showed an under prediction bias due to the wide variation of possible values for the cyclic degradation coefficient (CD) and the necessity of assuming a conservative value of CD in mixed system rating calculations.  This report includes detailed measurement data for the tested evaporators and an uncertainty analysis of the rating methodology.


 