HVAC&R Equipment Performance Group
Publications
An Improved Two-Phase Pressure Drop Correlation for 180° Return Bends
An Improved Two-Phase Pressure Drop Correlation for 180° Return Bends
C. Hermes. and Domanski, P.A.
3rd Asian Conference on Refrigeration and Air-Conditioning, Gyeongju, Korea, May 21-23, 2006
Keywords:pressure drop, return bends, air conditioning, refrigeration, modeling
Abstract:A new correlation for two-phase pressure drop in 180º return bends is proposed based on a total of 241 experimental data points for R-22 and R-410A. The data span smooth tubes with inner diameters (D) from 3.25 mm to 11.63 mm, bend radii ® from 6.35 mm to 37.25 mm, and curvature ratios (2R/D) from 2.32 to 8.15. The correlation predicts all data with a mean deviation of 15.7 %, and 75 % of the data fall within ±25 % error bands.
|
Privacy Policy / Security Notice / Accessibility Disclaimer | FOIA | Information Quality | About NIST NIST is an agency of the U.S. Department of Commerce |